FREE BOOKS

Author's List




PREV.   NEXT  
|<   102   103   104   105   106   107   108   109   110   111   112   113   114   >>  
ures are placed in a line, fitting of not less than 45 deg. to the horizontal must be used on vent lines to prevent filling with rust or condensation; except on brick or tile walls, where it is necessary to channel same for pipes, 90 deg. fittings will be allowed. Trapped vent pipes are strictly prohibited. No vent pipe from the house side of any trap shall connect with the ventilation pipe or with sewer, soil or waste pipe. SEC. 31. OFFSET ON VENT LINES.--All offsets on vent lines must be made at an angle of not less than 45 deg. to the horizontal, and all lines must be connected at the bottom with a soil or waste pipe, or the drain, in such manner as to prevent the accumulation of rust, scale or condensation. No sheet metal, brick, or other flue shall be used as a vent pipe. SEC. 32. SETTING OF FIXTURES.--All fixtures must be set open and free from all enclosing woodwork. Water closets and urinals must not be connected directly or flushed from the water-supply pipes except when flushometer valves are used. Each water closet must be flushed from a separate cistern, the water from which is used for no other purpose, or may be flushed through flushometer valves. Rubber connection and elbows are not permitted. Pan, plunger, or hopper closets will not be permitted in any building. No range closet either wet or dry, nor any evaporating system of closets shall be constructed or allowed inside of any building. A separate building constructed especially for the purpose, must be provided in which such range closets shall be set. All earthenware traps must have heavy brass floor flange plates, soldered to the lead bends and bolted to the trap flange, and the joint made permanently secure and gas-tight. In all buildings sewer-connected there must be at least one water closet in each building. There must be a sufficient number of water closets so that there will never be more than 15 people to each water closet. Separate water closets and toilet rooms must be provided for each sex in buildings used as workshops, office buildings, factories, hotels and all places of public assembly. In all buildings the water closet and urinal apartments must be ventilated into the outer air by windows opening on the same l
PREV.   NEXT  
|<   102   103   104   105   106   107   108   109   110   111   112   113   114   >>  



Top keywords:

closets

 

closet

 
building
 

buildings

 

connected

 

flushed

 

valves

 

flange

 

flushometer

 
allowed

separate
 

permitted

 

constructed

 
horizontal
 
prevent
 

condensation

 

purpose

 
provided
 

bolted

 
evaporating

system

 
permanently
 
earthenware
 

plates

 

inside

 

soldered

 
Separate
 

public

 

assembly

 
urinal

places
 

hotels

 

office

 

factories

 

apartments

 

ventilated

 

windows

 

opening

 

workshops

 
sufficient

number
 
toilet
 

people

 

secure

 

OFFSET

 
ventilation
 

connect

 

bottom

 

offsets

 

prohibited